+91 9586406095
Manufacturer: ABB
Model / Part Number: A26-30-10
Coil Voltage:
230–240 V AC (50 Hz)
240–260 V AC (60 Hz)
Insulation Voltage ($U_i$): 1000 V~
Thermal Current ($I_{th}$): 45 A
Rated Operational Current ($I_e$ AC-1): 45 A
General Use Rating (UL/CSA): 40 A
Rated Operational Power (AC-3):
6.5 kW @ 230 V
11 kW @ 400 V
15 kW @ 500 V
15 kW @ 690 V
Rated Operational Power (AC-8a without TOR): 15 kW @ 400 V
3-Phase Motor Ratings (UL/CSA):
7.5 HP @ 200 V
10 HP @ 240 V
20 HP @ 480 V
25 HP @ 600 V
1-Phase Motor Ratings (UL/CSA):
2 HP @ 120 V
5 HP @ 240 V
Standards & Certifications: IEC/EN 60947-4-1, CE, UL Listed (IND. CONT. EQ. 247C), CSA (600 Vac MAX. Breaking all lines)
Auxiliary Contacts: 1 NO (13NO - 14NO) / AUX. CONT. A600 P300
Wiring / Wire Range: AWG 8–12 Cu STR 75°C
Terminal Tightening Torque: 15 lb.in / 1.7 Nm
Short-Circuit Protection / Fuse: Suitable for use on a circuit capable of delivering not more than 5 kA rms, 600 V max., 90 A time delay fuse. Compatible with TA25 Series Overload Relays.
Country of Origin: Made in India
Condition: Used
Marine Industry
Industrial Automation
Control Panels
Manufacturing Plants
Oil & Gas Industry
Power Plants
Chemical Plants
Process Automation
Is this product new?
No, it is used / pre-owned.
Is this original product?
Yes, it is a genuine original ABB product.
Is international shipping available?
Yes, international worldwide shipping is available.
Can you provide bulk quantity?
Depends upon stock available.
Can you share additional product images?
Yes, available on request.
These other products might interest you